Helium-based cooling concept of the ET-LF interferometer
Author
Lennard Busch, Xhesika Koroveshi, Steffen Grohmann
Participating institute
Institut für Technische Thermodynamik und Kältetechnik (TTK)
Institut für Beschleunigerphysik und Technologie (IBPT)
Fakultät für Chemieingenieurwesen und Verfahrenstechnik (CIW)
Genre
Description
The low-frequency interferometer in the Einstein Telescope (ET-LF) shall be operated at test mass temperatures of 10 K to 20 K. Motivated by the potential of using superfluid helium (He-II) for cooling the test masses, we derive a general cooling concept for the ET-LF cryostats. This concept is based on a helium refrigerator in each ET corner point, providing cooling capacity with He-II for the test masses at 2 K, as well as cooling capacity with normal helium (He-I) for radiation screens at 5 K and thermal shielding at 50 K to 80 K. The heat extraction path of the 2 K system is implemented by means of long capillaries, where the heat transport takes place by steady-state heat conduction in He-II. The integration of He-II filled capillary suspensions in the payload design may also offer a solution for achieving low temperatures of the test masses. This option will be investigated in terms of thermal dissipation and the propagation of vibrational noise from the helium cooling system into the payload.
Duration (hh:mm:ss)
00:22:07
Published on
26.05.2021
Subject area
License
Resolution | 1916 x 1080 Pixel |
Aspect ratio | 479:270 |
Audio bitrate | 128246 bps |
Audio channels | 2 |
Audio Codec | aac |
Audio Sample Rate | 48000 Hz |
Total Bitrate | 1071991 bps |
Color Space | yuv420p |
Container | mov,mp4,m4a,3gp,3g2,mj2 |
Media Type | video/mp4 |
Duration | 1327 s |
Filename | DIVA-2021-189_unknown.mp4 |
File Size | 177.802.060 byte |
Frame Rate | 25 |
Video Bitrate | 937701 bps |
Video Codec | h264 |
Media URL
Embed Code